How to size a cable: current, length and voltage drop
A cable that's too thin for its length doesn't just risk overheating – it can lose enough voltage over the run that equipment at the far end underperforms or trips out. Here's the calculation method BS 7671 is built around, and where its limits are.
8 min read · Updated: 7 September 2026
Key points
- Cable sizing has two separate checks: current-carrying capacity (can the conductor carry the load without overheating) and voltage drop (does too much voltage get lost over the run). Both must pass – neither alone is sufficient.
- BS 7671, the UK Wiring Regulations, limits voltage drop to 3% for lighting circuits and 5% for other circuits, measured from the origin of the installation to the equipment.
- A 32 A single-phase circuit over a 20 m run, on 2.5 mm² copper, has a voltage drop of about 2.48% at 230 V – within the 5% limit but with limited headroom for a longer run.
- Doubling the cable run roughly doubles the voltage drop for the same conductor size and current – a 32 A, 20 m run needing 2.5 mm² needs 4 mm² at 30 m for the same 3% drop target.
- Voltage drop and current-carrying capacity are calculated independently, and current-carrying capacity depends heavily on installation method (clipped direct, in conduit, in insulation) – this article covers the voltage-drop calculation; capacity ratings must be checked separately against BS 7671 tables for the actual installation method used.
Two separate checks, not one
Sizing a cable correctly means passing two independent checks, and the larger of the two required sizes is the one that's actually used. The first is current-carrying capacity (sometimes called ampacity): whether the conductor can carry the design current continuously without its insulation overheating, which depends on the installation method – clipped to a surface, run in conduit, buried, or in contact with thermal insulation all give different capacity ratings for the same cable size. The second is voltage drop: whether too much voltage is lost as heat along the length of the cable before it reaches the load.
A short, heavily loaded cable is often limited by current-carrying capacity; a long, lightly loaded cable is often limited by voltage drop instead. Both checks use the same starting inputs – current and cable length – but they're separate calculations with separate rules, and BS 7671, the UK Wiring Regulations (BS 7671:2018+A2:2022), requires both to be satisfied.
What this article covers
This guide focuses on the voltage-drop calculation, which is straightforward arithmetic from current, length and cable material. Current-carrying capacity depends on the specific installation method and must be checked against the relevant BS 7671 Appendix 4 table for that method – it isn't covered by the voltage-drop formula below.
The voltage-drop formula
For a single-phase or DC circuit, the voltage drop over a cable run is calculated as: ΔU = (2 × L × I × cos φ) / (γ × A), where L is the one-way cable length in metres, I is the current in amps, cos φ is the power factor (1 for DC or purely resistive loads), γ is the conductor's conductivity (56 m/(Ω·mm²) for copper at normal operating temperature, 35 for aluminium), and A is the cross-sectional area in mm². For a three-phase circuit, the factor of 2 is replaced with √3 (approximately 1.73), since three-phase power delivery loses proportionally less voltage per amp over the same cable.
Rearranged to find the minimum required cross-section directly: A = (2 × L × I × cos φ) / (γ × ΔU_max), where ΔU_max is the maximum allowed voltage drop in volts (the percentage limit converted to volts at the supply voltage). The result is then rounded up to the next standard conductor size – 1.5, 2.5, 4, 6, 10, 16, 25 mm² and so on, per IEC 60228.
BS 7671 voltage drop limits
BS 7671 sets maximum permitted voltage drop from the origin of an installation (the consumer unit or distribution board) to the point of use: 3% for lighting circuits and 5% for other circuits, on a low-voltage supply. At the standard UK domestic supply of 230 V, that's a maximum of 6.9 V for lighting and 11.5 V for other circuits.
BS 7671 voltage drop limits at 230 V single-phase
| Circuit type | Maximum voltage drop (%) | Maximum voltage drop at 230 V (V) |
|---|---|---|
| Lighting circuits | 3% | 6.90 V |
| Other circuits (sockets, cookers, etc.) | 5% | 11.50 V |
Worked example: 32 A circuit, 20 m run
Take a single-phase 230 V circuit carrying 32 A over a 20 m one-way run, copper conductor, power factor 1 (a resistive or near-resistive load), with a 3% drop limit. Applying the formula, the required cross-section works out to 3.31 mm², which rounds up to the next standard size, 2.5 mm² only if it's sufficient – here it isn't quite, so the calculation rounds up to 4 mm². Checking the actual drop on 4 mm²: ΔU = (2 × 20 × 32 × 1) / (56 × 4) = 5.71 V, which is 2.48% of 230 V – within the 3% limit, with roughly 0.5 percentage points of headroom.
Required cable size by run length, 32 A single-phase copper circuit, 3% drop limit at 230 V
| One-way length (m) | Required cross-section (mm²) | Recommended standard size (mm²) | Actual voltage drop (%) |
|---|---|---|---|
| 10 | 1.66 | 2.5 | 1.99% |
| 20 | 3.31 | 4 | 2.48% |
| 30 | 4.97 | 6 | 2.48% |
The relationship is close to linear: doubling the length from 10 m to 20 m roughly doubles the required cross-section, and the actual drop on the recommended size stays in a similar range (1.99% to 2.48%) because each step rounds up to the next standard size rather than landing exactly on the limit.
Copper vs. aluminium
Aluminium conductors have lower conductivity than copper (35 versus 56 m/(Ω·mm²)), so an aluminium cable needs a larger cross-section than copper for the same current, length and drop limit. On the same 32 A, 20 m, 3% example above, copper needs 4 mm²; aluminium needs 5.30 mm², rounding up to 6 mm² – one standard size larger. Aluminium is lighter and often cheaper for a given current rating on longer runs, which is why it's common in larger supply cables, but it needs a bigger cross-section than copper to do the same job.
Size your own cable run
Enter the current, cable length, material and allowed voltage drop, and the calculator returns the required cross-section and the standard size to use.
Go to the cable size calculatorReference method C: typical current-carrying capacities
For context, BS 7671 Table 4D5 gives current-carrying capacities for twin-and-earth copper cable under Reference Method C (clipped direct to a surface, no thermal insulation contact): approximately 20 A for 1.5 mm², 27 A for 2.5 mm², 37 A for 4 mm², 47 A for 6 mm², 64 A for 10 mm² and 85 A for 16 mm². These figures assume the standard 30°C ambient temperature with a single circuit and no grouping or insulation effects – a real installation is often derated below these figures if the cable runs through loft insulation, is grouped with other circuits, or sits in a hotter ambient environment, and the correct derated figure always comes from the full BS 7671 Appendix 4 tables for the actual installation conditions, not from this list.
Voltage drop passing doesn't mean the cable is safe to install
A cable can easily pass the voltage-drop check on cross-section alone while still being undersized for current-carrying capacity once the correct installation method, grouping and ambient temperature are applied – for example, the same 4 mm² cable rated at 37 A clipped direct can drop to around 23 A if it runs through thermal insulation. Both checks are mandatory under BS 7671, and installation work should be carried out or verified by a competent, registered electrician.
Where this calculation stops being enough
The voltage-drop method above covers straightforward, single-circuit runs at a known ambient temperature. It doesn't account for grouping factors (multiple cables bundled together, which reduce each cable's safe current), thermal insulation contact, ambient temperature correction, protective device coordination (making sure a fuse or circuit breaker disconnects fast enough under fault conditions), or earth fault loop impedance – all separate checks required under BS 7671 for a compliant installation. This calculation is a useful planning and verification tool, not a substitute for a full design carried out by, or checked against the work of, a qualified electrician working to the current edition of BS 7671.
Frequently asked questions
How do I calculate the cable size I need?
Two checks are required: current-carrying capacity for the installation method used, and voltage drop over the run length. The voltage-drop formula is A = (2 × L × I × cos φ) / (γ × ΔU_max) for single-phase, using the larger of the two results as the required size.
What is the maximum voltage drop allowed under BS 7671?
3% for lighting circuits and 5% for other circuits, measured from the origin of the installation to the point of use. At 230 V, that's 6.90 V and 11.50 V respectively.
What size cable do I need for a 32 A circuit over 20 m?
On copper, 20 m one-way, 3% drop limit, the calculation requires 3.31 mm², rounding up to the standard 4 mm² size, giving an actual drop of about 2.48%. Current-carrying capacity for the specific installation method must also be checked separately.
Why does a longer cable run need a bigger cross-section for the same current?
Voltage drop is proportional to length: doubling the run roughly doubles the voltage lost for the same conductor size and current, so a longer run needs a larger cross-section to keep the drop within the same percentage limit.
Does aluminium cable need to be thicker than copper?
Yes. Aluminium has lower conductivity (35 versus 56 m/(Ω·mm²) for copper), so it needs a larger cross-section than copper for the same current, length and voltage-drop limit – often one standard size larger.
Is voltage drop the only thing that determines cable size?
No. Current-carrying capacity, which depends on the installation method (clipped direct, in conduit, in insulation, grouped with other cables), must also be checked. The larger of the two required sizes – voltage drop or current-carrying capacity – is the one that's used.
Can I use this calculation to install a cable myself?
The voltage-drop calculation is a useful planning tool, but a compliant installation under BS 7671 also requires checks on current-carrying capacity for the actual installation method, protective device coordination and earth fault loop impedance. Installation work should be carried out or verified by a competent, registered electrician.
Sources
Related articles
Convert your own figures
Enter the apparent power in kVA and the power factor to get the real power in kW, or the other way round.
Go to the kVA ↔ kW converter